Controller pack
Service Manual
92
Heatpump control functions
SMGB0066 rev.0 - 12/2009
 
WhenthereisademandforheatingorDHW,theSystemControllerwillsendtotheheatpumpasignalfortherequired
Heat Pump outlet temperature. The System controller uses the 4-20mA connection to represent the outlet water 
temperature setpoint. The heatpump will modulate the appliance according to its own control strategy to achieve the 
correct output water temperature.
A conversion table from water temperature setting to mA signal is provided at the end of this guide.
Heat Pump Supply Setting = SSUP (supply setpoint) + P31 (Heat Pump Sensor Offset)
The Heat Pump Supply setting is always constrained within the maximum and minimum heat pump supply temperatures. 
These limits depend on the current outside temperature; see “Heat Pump Operating Limits”. Heat Pump Sensor Offset is 
explained in the next section.
EP6  Heat Pump Supply Setpoint at 4mA (default 20°C)
EP7  Heat Pump Supply Setpoint at 20mA (default 55°C)
These parameters should only be changed with the approval of the manufacturer.
note
Engineering Parameters (EP) are only available for service engineers. -
 
Inpractice,theremaybeadifferencebetweentheheatpumpoutlettemperature(measuredbytheHeatPump)andthe
supply temperature (measured by the system controller). This can be caused by:
Different measuring position. The Heat Pump is outside and some loss of heat is possible between the heat pump 1. 
and the supply pipes inside the house.
Different types of sensor. The Heat Pump measures the outlet temperature using an immersion-type sensor directly 2. 
inthewaterowafterthecondenser.TheSystemControllerusesastrap-ontypesensor,whichdependingonthe
ambientconditions,willtypicallymeasurealowertemperaturethananimmersion-typeinthesamelocation.
Thisdifferenceneedstobetakenintoaccountforoptimumcontrolperformance,andparameterP31isprovidedsothis
canbeadjustedaccordingtotheinstallation.
P31   Heat Pump Sensor Offset (default 3K)