Controller pack
Service Manual
80
Systemconguration,settingsandcontrolsystem
SMGB0066 rev.0 - 12/2009
Thisisabivalentsystemwheretheboilerisconguredinparallelwiththeheatpump.Ahydraulicseparatororbuffer
tankhastobeusedtoensureproperhydraulicbalancing.Thissystemisrecommendedforretrot(upgrade)applications
where an existing gas/oil boiler will be retained to provide the full heating requirements on the coldest days of the year.
CONF = 4
P4 = heating curve according to building and system characteristics.
DHW tank control is not possible with this system.
Itisalsorecommendedtoreviewallparametersettings,andmakemodicationsasrequiredbytheinstallation.
Bi-Valent System with DHW & mixed heating loop.
Hydraulic separator or buffer tank.
CONF=4 Bi-valent Parallel system
Thisisabivalentsystemwheretheboilerisconguredinserieswiththeheatpump.Ahydraulicseparatororbuffertank
hastobeusedtoensureproperhydraulicbalancing.Thissystemisalsousedforretrot(upgrade)applications,but
operateslikethemono-energeticsystemusingthegas/oilboiler,similarlytotheelectricheater,inserieswiththeheat-
pump. The boiler only needs to provide the additional peak load capacity
CONF = 5
P1=0,1,2accordingtoDHWsystemtype.
P4 = heating curve according to building and system characteristics.
Itisalsorecommendedtoreviewallparametersettings,andmakemodicationsasrequiredbytheinstallation.
Bi-Valent System with DHW.
Serial operation with bypass/mixing valve.
DHW controlled by diverting valve
Hydraulic separator or buffer tank.
CONF=5 Bi-valent Parallel system
P1=1 DHW valve