Available Optional
functions
Service Manual
154
Power save mode
SMGB0066 rev.0 - 12/2009
Compressorstartupbythermorecoveryshallalwaystoensure3minutesofcompressorOFFstatus.However,thestandard
uponoperationstartupis3minutesbutitcanbe,changedbythesettingmodeinthefollowingchart.Thetimeavailablefor
settingis30seconds,andby1minutebetween1and10minutes.
This mode is activated by turning pin 3 of DSW1 to ON.
Pressing PSW2 and PSW1 for more than three seconds at the same time allows changing from each item displayed. To
nishchangingtopredeterminedsetting.
The chart of setting operation is shown below.
PSW1
PSW1
PSW1 PSW1
PSW1
PSW1
PSW2
PSW2
PSW2
PSW2
PSW2 PSW2
PSW1
PSW2
PSW1: Valve up
PSW2: Valve down
Whenpowersavemodeisselectedwith“DSW4-6”ON,thefrequencyupperlimitforeachHPchangesfrom“Standard”-->
“PowerSaver”(i.e.,frequencyupperlimitlowersby10%).
Thismodeonlychangesthefrequencyupperlimitofthecompressor,anddoesnotaffecttoothercongurations.
DSW ON/OFF determination is performed only immediately after the Power activation.