167
Initial troubleshooting
SMGB0066 rev.0 - 12/2009
Troubleshooting
Service Manual
7
System controller cable disconnected Connect the cable
Replace the cable or repair the
cable
One(orseveral)phasefailure,orinvertedphaseorder("” alarm).
Only in three phase unit.
ChecktheconnectionofR,S
and T phase.
Reorder the phases
Failure of remote/local switch or remote/local switch set at “local” Check remote/local switch
Turn the switch to “remote” or
replace switch
Decientcontactatterminal
controller connectors
Insufcientconnectionorincorrect
connection of the Yutaki unit PCB
Check the connectors and
terminals
Removerust,dustorany
contaminants,checkthe
correct tightening of the
terminals
Insufcientconnection
or incorrect connection of the terminal
in remote controller
Failure of the system controller Refer to “Troubleshooting of system controller”
UndenedPCBfailure
Unconnected wires to PCB Check the connectors Correctly connect the wires
Failure of PCB
Check PCB through its self-
diagnostic mode
Replace PCB if it failed
Incorrect wiring connection
Take action according to the procedure that is displayed in
"TEST RUN"