Troubleshooting
Service Manual
184
Troubleshooting procedure
SMGB0066 rev.0 - 12/2009
↔
• ThealarmcodeisdisplayedonthePCB´sdisplay.
• Thecompressorstopsandrestartsautomaticallyin3minutes.
• Thealarmappearsafter3retriesduring30minutes.
– This alarm code is displayed when the suction gas temperature (Ts) is lower than -5ºC during 10 seconds. (Only
cooling operation).
Are the connector CN11
on the PCB2 and suction
gas temperature thermistor
correctlyconnected?
Wiring check and repair
No
Yes
Measure the temperature
of the position where the
suction gas thermistor
attached,bysurface
thermometer.
Is the temperature measured
and shown in segment
proper?
Yes
Checkthewaterowrate
(Check temperature of inlet and outlet)
No
Clogging of water strainer
Pump reverse rotating check
Check the air mixing
Are the connectors
between PCB1 and PCB2
correctlyconnected?
PCB1
CN9-CN1
PCB2
CN5-CN2
CN6-CN3
CN2-CN4
No
Wiringcheck,Repair.
(Breakingofwire,wrong
wiring)
Yes
Shortage of Refrigerant/ Gas leakage
Clogging of low pressure pipe
Clogging of expansion valve
Pull out connector
and measure thermistor
resistance.
Isresistancecorrect?
No
Replace thermistor
Yes
Check PCB2
Check water temperature (not excessively
low)
Malfundtion of check valve
Malfunction of expansion valve