Troubleshooting procedure
SMGB0066 rev.0 - 12/2009
Troubleshooting
Service Manual
7
• ThealarmcodeisdisplayedonthePCB´sdisplay.
• Thealarmappearsafter3retriesduring30minutes.
– Thisalarmcodeisdisplayedwhenthevoltagebetweenterminal"P"and"N"ofDIP-IPMisinsufcient.
warning
Electrical hazard. Risk of electrical shock. Be extremely carefull because of the high voltage - .
Is the Power Supply voltage
230V±10%?
No
Yes
No
Yes
Is connection correctly
between DIP-IPM and
capacitors(CB1andCB2),
DCLorCMC?
No
No
Yes
Does LED201 on DIP-
IPM ON after compressor´s
magnetic contactor (CMC)
turnON?
*1):Ifthecapacitorhasahighvoltage,performthehigh-voltagedischargepocedure.
Refer to section RHUE-(3~6)AVHN: "Procedure for checking the DIP-IPM".
*2):CheckingproceduresofthediodemodulearedisplayedinitemRHUE-(3~6)
AVHN: "Procedure for checking the DIP-IPM".
Restart the operation
Is the voltage over 187V
duringoperation?
Yes
Does the voltage fall during
the operation because of the
operationofotherapparatus?
Yes
No
No
IstheDCvoltageover240V?
Check the wiring and the
cable capacity
Check the wiring DIP-IPM
andcapacitors(CB1,2)*2).
Incasethewiringiscorrect,
replace the DIP-IPM
Faulty DIP-IPM. Replace it.
Checkcapacitors(CB1,2).
Yes
Normal
Faulty
Replace the capacitors.
Capacitors have high voltage.
Beextremelycarefull*1).
Connect correctly.
How is the
compressor
operation?
Faulty DIP-IPM.
Replace it.
Compressor stops when
frequency increases.
(Aprox. 20 Hz to 60 Hz)
Compressor stops
immediately.
(Lower than 20 Hz)
Frequency can increase
higher than 60 Hz