193
Troubleshooting procedure
SMGB0066 rev.0 - 12/2009
Troubleshooting
Service Manual
7
1
• ThealarmcodeisdisplayedonthePCB´sdisplay.
– This alarm code is displayed when the water temperature is above 59ºC during compressor operation. (Only heating
operation).
Are connectors CN9 and
CN13 on the PCB2 correctly
connected?
Wiring Check
(Breakingofwire,wrong
wiring)
No
Yes
Is the actual water
temperature and the
temperature shown in
segmentproper?
Yes
No
Check pump reverse rotation
Check water strainer clogging
Check air mixing
Are the connectors
between PCB1 and PCB2
correctlyconnected?
PCB1
CN9-CN1
PCB2
CN5-CN2
CN6-CN3
CN2-CN4
No
Wiringcheck,Repair.
(Breakingofwire,wrong
wiring)
Yes
Pull out connector
and measure thermistor
resistance.
Isresistancecorrect?
No
Replace thermistor
Yes
Check PCB1 and PCB2
Checkthewaterowrate
(Check temperature of inlet and outlet)
Check chilled water thermostat setting value
(It shall be within the working range)