Troubleshooting
Service Manual
206
Troubleshooting procedure
SMGB0066 rev.0 - 12/2009
• ThealarmcodeisdisplayedonthePCB´sdisplay.
• Thecompressorstopsandrestartsautomaticallyin3minutes.
• Thealarmappearsafter6retriesduring30minutes.
– This alarm code is displayed when the compressor current is higher than the set value.
Restart the
operation. Does it
tripimmediately?
Check ISPM
orDip-IPM?
Turnoffpower,
disconnectU,V,Wfrom
compressor terminals and
restart. Does the protecting
functionactivate?
Check compressor
Check power supply
and wiring capacity.
Check compressor
Replace ISPM or Dip-
IPM
Yes
No
No
No
Yes
No
Check ISPM
Yes
No
Check power supply.
Is the current value which
activating,morethan
settingvalue(70.5A)?
Is there any
factor which
instantaneous
voltage drop
happened?
Is the input current of
each phase almost same
inall3phase?
No
(Trip after while)
No
Yes
Check power supply
and wiring capacity
No
Yes
Replace ISPM or Dip-
IPM
Is the power supply
voltage higher than 170V
duringoperation?
Is the power supply
voltage higher than
170Vduringoperation,
even if the other
appliancestarts?
No
Yes
Is the power supply
voltage230V±10%?
Yes
(Trip
immediately)
No
(Trip happen
sometimes)
caution
Electrical hazard. Risk of electrical shock. Before checking and replacing the inverter parts perform the high -
voltage discharge procedure by referring to section "Checking procedure for main parts".