Troubleshooting procedure
SMGB0066 rev.0 - 12/2009
Troubleshooting
Service Manual
7
• Thecompressorstopswhenthetemperatureofthethermistorforinverterfinexcess100ºC,andrestartsautomatically
in 3 minuntes.
• Thealarmappearsafter3retriesduring30minutes.
1*):Performthehighvoltagedischargeworkbyreferringtothesection"Checkingprocedureformainparts"before
checking and replacing the inverter components.
No
Replace the dipIPM or
ISPM.*1)
Restart the operation.
Doesittripsoon?
Yes
Remove the clogging
Is the air side heat
exchanger of the
outdoorunitclogged?
FaultyDipIPMorISPM,or
thermistor.
Replace it.
No
Is thermistor short circuit or
faulty?
No
Yes
Replace the thermistor
Yes