211
Troubleshooting procedure
SMGB0066 rev.0 - 12/2009
Troubleshooting
Service Manual
7
• ThealarmcodeisdisplayedonthePCB´sdisplay.
• Itisavailableoncefeedbacksignalconrmed.
– This alarm code is displayed when the Pump operation feedback signal (terminals 1-2) is OFF during pump interlock
(CMp) ON (terminals 3-4).
Is thermal relay for pump
(TRP)activated?.(Ifuseda
eldsuppliedpump)
Yes
No
Is 220-240V the voltage
between connector PCN4
PIN1andPIN3onPCB1?
No
Yes
Check Printed Circuit Board
(PCB1)
Check the Pump Lock
Check thermal relay for pump
Check wiring around pump
and thermal relay for pump