Troubleshooting
Service Manual
214
Troubleshooting procedure
SMGB0066 rev.0 - 12/2009
U
• Watertemperatureisincreasedto65ºCbyheatgenerationinpumporotherheatsourceduringonlypumprunning
(during compressor stop: during thermo off or during pump automatic operation in winter).
• Ifwatertemperatureisdecreasedlessthan6ºCduetopumpstop,itbecomesnormalstatusautomatically.
• Sincethisisnotanabnormalityofunit,itisnotsavedinalarmhistory.
Whenthisalarmhappen,checkthewatersystemrst.Ifanycausecannotbedetected,checktheunitaccordingto
the following procedure.
note
Measure the resistance at least in 2 different points which is different more than 10 ºC. -
Are the connectors between
PCB1 and PCB2 correctly
connected?
PWB1
CN9-CN1
PWB2
CN5-CN2
CN6-CN3
CN2-CN4
No
Yes
Pull out connector
and measure thermistor
resistance.
Isresistancecorrect?
No
Replace thermistor
Yes
Are connectors CN3 and CN9
onPCB2correctlyconnected?
No
Yes
Wiringcheck,Repair.
(Breakingofwire,wrongwiring)
Wiringcheck,Repair.
(Breakingofwire,wrongwiring)
Failure of PCB1.
Replace PCB1.
Is the actual water temperature
and the water temperature shown
insegmentproper?
Yes
No
Check water system of heat load
side
PCBmonitoringposition:PCB2,CN3andCN9