Accessories hydraulic installation
SMGB0066 rev.0 - 12/2009
Water pipe
installation
Service Manual
2
Inordertopreventthis,duringshutdownperiodsitisusefultoemptythewaterfromtheinstallation.
note
In cases where water drainage is difcult, an antifreeze mixture of glycol (ethylene or propylene) should be used -
(content between 10 % and 40 %).
The performance of the unit working with glycol may decrease in proportion to the percentage of glycol used, -
since the density of glycol is higher than that of water.
1G” Water OUT
Water IN
1G”
1/4G”
- Inlet and outlet connection pipes must be 1G”
- Itmustbekeptthewaterowdirectionindicatedinpreviousdrawing
note
Check periodically: -
Water ow and pressure -
Water leakages -
Fixing points tightening -

 
The following problems should occur when the quantity of water in the forced circulation system (1) on water side is
insufcient.
WEH frequently ON/OFF cycles affecting Yutaki performance.1.
Lowtemperatureinwatercirculationsystematdefrosting,whichshouldcauseanalarm(freezeprotection).2.
LWPS or Cut-Out thermostat activation due to low water pressure (< 1 bar) or due to excessive high water 3.
temperature inside WEH.