Ease of Commissioning
l Easy aiming with graduated mount
l Easy guided setup via HART®, RS-485 or USB / PC Application
l Simple test with test lamp
Ease of Maintenance
l Simple bump test with Honeywell® long range test lamps (simply test at height)
l Built-in test diagnostics certified to IEC61508
l Advanced window monitoring
l No need to calibrate
l Plug and Play design for ease of installation and maintenance
Self-Test
The FS24XPlus™ executes a self-test sequence every minute. All optical sensor channels and the
related processing of sensor data are evaluated to ensure that analog circuits, processors, and
memory are functional. Depending on the function, tests are repeated several times to confirm
device status prior to declaring a fault. In the case of the optical self-test, which evaluates the optical
system by flashing an IR LED and monitoring the reflection from the window, a fault in not declared
until a total of 5 consecutive test attempts have failed. This takes a total of five minutes to complete.
Additional self-tests are conducted on a continuing basis to ensure the continuity of relay coils.
Available Spares/Accessories
l SM4 Swivel Mounting Bracket
l SM4-M Marine Swivel Mounting Bracket
l SH-001 Sunshade
l FVR-01 Field of View Restrictor
l TL-1055 safe area test lamp
l TL-2055 hazardous area test lamp
l Electronics module replacement
l NFPA 72 Connector Kit p/n FS24XP-NFPA-KIT
Honeywell®FS24XPlus™ | User Manual