EasyManua.ls Logo

Honeywell FS24X Plus - Command #164: Read Event History

Honeywell FS24X Plus
107 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Honeywel FS24XPlus™ | User Manual
78
Command #164: Read Event History
Reads Event History Logs.
Request Data Bytes
Byte Format Description
0 Integer Warning or Fault type
1 Integer Event direction
2 Integer Login level
Response Data Bytes
Byte Format Description
0 Integer Warning or Fault Type
1 Integer Event direction
2 Integer Login level
3-7 Integer Event Index
8-11 ASCII Time
12-15 Integer Event Arg 1
16-19 Integer Event Arg 2
Command-Specific Response Codes
Code Class Description
0 Success No Command-Specific Errors
1 Undefined
2 Error Invalid Selection
3 Error Parameter Too Large
4 Error Parameter Too Small
5 Error Too few data bytes received
6 Error Transmitter Specific Command Error
7 Error Write Protect Mode
8-15 Undefined
16 Error Access Restricted
17-31 Undefined
32 Error Busy
33-127 Undefined

Table of Contents

Related product manuals