Command #144: Read Model
Reads the short tag.
Request Data Bytes
Byte Format Description
None
Response Data Bytes
Byte Format Description
0-5 Packed ASCII Default {25,60,180,97,8,32}Packed ASCII "FS24XPlus™"
Command-Specific Response Codes
Code Class Description
0 Success No Command-Specific Errors
1-7 Undefined
8 Error Access Restricted
9-15 Undefined
16 Error Access Restricted
17-127 Undefined
Command #153: Read Device Alarm State
Reads the Device Alarm State.
Request Data Bytes
Byte Format Description
None
Response Data Bytes
Byte Format Description
0 Enum
[0] - Device Alarm Status
0 - Alarm2
1 - Alarm1
4 - None