Command #183: Read mA Configuration
Reads mA Configuration.
Request Data Bytes
Byte Format Description
0-1 Integer Inhibit Timeout
Response Data Bytes
Byte Format Description
0-3 Float Fault Current
4-7 Float Warning Current
8-11 Float Alarm1 Current
12-15 Float Alarm2 Current
16-19 Float Inhibit Current
20-23 Float Background IR Current
24-27 Float Background IR Current
28-31 Float Normal Current
Command-Specific Response Codes
Code Class Description
0 Success No Command-Specific Errors
1 Undefined
2 Error Invalid Selection
3 Error Parameter Too Large
4 Error Parameter Too Small
5 Error Too few data bytes received
6 Error Transmitter Specific Command Error
7 Error Write Protect Mode
8-15 Undefined
16 Error Access Restricted
17-31 Undefined
32 Error Busy
33-127 Undefined
Honeywell®FS24XPlus™ | User Manual