12 S3 Series UL Listing Document — P/N LS10005-051GF-E:D3 3/09/2016
Installation Wiring SLP-E3 Main Circuit Installation Wiring Diagram
TB4-5 SUPV NO Supervisory relay contact normally OPEN N/O
TB4-6 SUPV C Supervisory relay contact common
TB4-7 TRBL NC Trouble relay contact normally CLOSED N/C
TB4-8 TRBL NO Trouble relay contact normally OPEN N/C
TB4-9 TRBL C Trouble relay contact common
TB5-1 RS-232 GND For Programming, GND connects to red lead on the
download cable P/N 75267.
For Printer Port, GND connects to printer DB-9, PIN-5.
RS-232
Download or
Printer Port
(See Note 2)
TB5-2 RS-232 TxD For Programming, TxD connects to black lead on the
download cable P/N 75267.
For Printer Port, TxD connects to printer DB-9, PIN-2.
TB5-3 RS-232 Supervision Optional printer supervision.
For Printer Port, SUPV connects to printer DB-9, PIN-4.
TB5-4 RS-232 RxD For Programming, RxD connects to green lead on the
download cable P/N 75267.
For Printer Port, RxD connects to printer DB-9, PIN-3.
TB6-1 BAT + Positive power for battery connection
TB6-2 BAT - Negative power for battery connection
J1 AC SUPV / + 24 Power supply input connection
J2 ETHERNET RJ45 10/100 Ethernet connection for configuration downloading and /or
FocalPoint connection (See Note 3)
J4 NETWORK Connects to J10 of the RPT-E3-UTP
J5 SLC-PM Loop 1 SLC-PM Card connection for Loop 1
J6 SLC95-PM Loop 2 SLC95-PM Card connection for Loop 2
J7 LOCAL DISPLAY Local Display (LCD-SLP) connection. Connects to J5 of the LCD-SLP.
SW1-1 SLC 1 Disconnect SLC1 disconnect (ON to disconnect, normally OFF) (See Note 4)
SW1-2 SLC 2 Disconnect SLC2 disconnect (ON to disconnect, normally OFF) (See Note 4)
SW1-3 NAC 1-NAC 4
Disconnect
NAC1-NAC4 disconnect (ON to disconnect, normally OFF) (See Note 4)
SW1-4 Buzzer Disable The main SLP-E3 Buzzer disable (ON to suppress local buzzer, normally
OFF on the SLP-E3) (See Note 4)
SW1-5 RS-232 BAUD Rate
Configure
RS-232 BAUD rate override (ON to force 115,200bps, OFF for configured
BAUD rate)
SW1-6 For Future Use Reserved
SW1-7 For Future Use Reserved
SW1-8 For Future Use Reserved
SW2 RESET System Reset button
SW3 SILENCE System Silence button
SW4 ARLM ACK System Alarm Acknowledge button
SW5 TRBL ACK System Trouble Acknowledge button
W1 MB/PR “MB” = For Masterbox/Releasing Solenoid
“PR” = For Polarity Reversal (See Note 1)
W2 AUX TERM OFF (Normal RS485 operation)
ON (RS485 Termination)
NOTES
NOTE 1: When you use the output for Releasing, verify Jumper W1 and configure within
CAMWorks. Refer to Releasing in the General Settings Section for proper operation.
NOTE 2: The RS-232 printer port connection cannot exceed 20 ft.; it must be in conduit and in the
same room as the panel. The PRN-7 Printer is a dot-matrix printer. It is shipped with a DB-9
Adapter Kit that provides the necessary hardware and cables for installation. For additional
information on the PRN-7 Printer, refer to the Manufacturer’s Installation Guide.
NOTE 3: When the Ethernet port is connected to FocalPoint, it cannot exceed 20 ft.; it must be in
conduit and in the same room as the panel.
NOTE 4: For Service Use Only.
Designation Description Comments
Table 2.2.1.1 SLP-E3 Main Circuit Board Installation Wiring Terminals (Continued)