18 S3 Series UL Listing Document — P/N LS10005-051GF-E:D3  3/09/2016
Installation Wiring Signaling Line Circuit (SLC) (SLC-PM/SLC95-PM)
2.6.2  SLC-PM Installation Wiring Diagram- System Sensor
Figure 2.6.2.1 illustrates the SLC-PM circuit board diagram. For system assembly and installation wiring ter-
minal designations, refer to the SLC-PM/SLC95-PM Installation Instructions, P/N: LS10044-000GF-E. You 
can download this document from the Gamewell-FCI Website (www.gamewell-fci.com).
 
Figure 2.6.2.1  SLC-PM Circuit Board
2.6.3  SLC-PM Installation Wiring Designations
Table 2.6.3.1 lists the SLC-PM installation wiring designations.
2.6.4  SLC-PM Signaling Line Circuit Specifications 
Table 2.6.4.1 lists the SLC-PM signaling line circuit specifications.
2.
Designation    Description  Comments
TB1-1 SLC A- Style 6, Style 7 RETURN (See Note 1)           
TB1-2 SLC A+ Style 6, Style 7 RETURN (See Note 1)
TB1-3 SLC B- Style 4/6, Style 7 OUT (See Note 1)
TB1-4 SLC B+ Style 4/6, Style 7 OUT (See Note 1)
J1 SLC-PM Loop 1 Connects to J5 of the SLP-E3 (See Note 2)
NOTE: For Style 4, use Terminals B+ and B- only. For Style 6, use terminals B+ and B- and 
connect RETURN wiring to A+ and A-. For Style 7 (Class X), wire the same as Style 6 and use 
the M500X Isolator Modules per the recommendations as required.
NOTE 2: Mount the SLC-PM board component side up. Insert the connector pins extending from 
J5 on the SLP-E3 to the J1 connector underneath the SLC-PM board. (For additional information, 
refer to the Warning and the SLC-PM/SLC95-PM Installation Instructions, 
P/N: LS10044-000GF-E). 
Table 2.6.3.1 SLC-PM Installation Wiring Designations
WARNING:  SLC-PM INSTALLATION TO SLP-E3 REQUIREMENT:
INSTALL THE SLC-PM BOARD COMPONENT SIDE UP.
Requirements SLC-PM Specifications
Circuit Supervision: Supervised
Circuit Power-Limited: Class 2 Power-Limited
Nominal Voltage, Frequency: 24 VDC (from FLPS-7 power supply)
Standby Current max. voltage, rated: 0.014 amp
Alarm Current: 0.014 amp
Identify the Manufacturer’s Name, Model 
designation for appliances to be used on the circuit 
or reference the device compatibility 
section/document.
Refer to the Compatibility Addendum to Gamewell-
FCI Manuals, P/N: 9000-0427-L8.
Max. Line Impedance: 40 Ohms and .5 µF line capacitance
Ground Fault Test Impedance: Zero Ohms
Impedance values and ground faults are 
annunciated.
GND FAULT LED or LCD-SLP
Identified by class or by class/style: One Class A, Style 6, Style 7 or Class B, Style 4 
signaling line circuit.
Table 2.6.4.1 SLC-PM Signaling Line Circuit Specifications