EasyManua.ls Logo

Honeywell Gamewell FCI S3 Series - 2: SLC-PM Installation Wiring Diagram- System Sensor; 3: SLC-PM Installation Wiring Designations; 4: SLC-PM Signaling Line Circuit Specifications

Honeywell Gamewell FCI S3 Series
60 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
18 S3 Series UL Listing Document — P/N LS10005-051GF-E:D3 3/09/2016
Installation Wiring Signaling Line Circuit (SLC) (SLC-PM/SLC95-PM)
2.6.2 SLC-PM Installation Wiring Diagram- System Sensor
Figure 2.6.2.1 illustrates the SLC-PM circuit board diagram. For system assembly and installation wiring ter-
minal designations, refer to the SLC-PM/SLC95-PM Installation Instructions, P/N: LS10044-000GF-E. You
can download this document from the Gamewell-FCI Website (www.gamewell-fci.com).
Figure 2.6.2.1 SLC-PM Circuit Board
2.6.3 SLC-PM Installation Wiring Designations
Table 2.6.3.1 lists the SLC-PM installation wiring designations.
2.6.4 SLC-PM Signaling Line Circuit Specifications
Table 2.6.4.1 lists the SLC-PM signaling line circuit specifications.
2.
SLC-PM
J1
TB1
1
4
Designation Description Comments
TB1-1 SLC A- Style 6, Style 7 RETURN (See Note 1)
TB1-2 SLC A+ Style 6, Style 7 RETURN (See Note 1)
TB1-3 SLC B- Style 4/6, Style 7 OUT (See Note 1)
TB1-4 SLC B+ Style 4/6, Style 7 OUT (See Note 1)
J1 SLC-PM Loop 1 Connects to J5 of the SLP-E3 (See Note 2)
NOTE: For Style 4, use Terminals B+ and B- only. For Style 6, use terminals B+ and B- and
connect RETURN wiring to A+ and A-. For Style 7 (Class X), wire the same as Style 6 and use
the M500X Isolator Modules per the recommendations as required.
NOTE 2: Mount the SLC-PM board component side up. Insert the connector pins extending from
J5 on the SLP-E3 to the J1 connector underneath the SLC-PM board. (For additional information,
refer to the Warning and the SLC-PM/SLC95-PM Installation Instructions,
P/N: LS10044-000GF-E).
Table 2.6.3.1 SLC-PM Installation Wiring Designations
!
WARNING: SLC-PM INSTALLATION TO SLP-E3 REQUIREMENT:
INSTALL THE SLC-PM BOARD COMPONENT SIDE UP.
Requirements SLC-PM Specifications
Circuit Supervision: Supervised
Circuit Power-Limited: Class 2 Power-Limited
Nominal Voltage, Frequency: 24 VDC (from FLPS-7 power supply)
Standby Current max. voltage, rated: 0.014 amp
Alarm Current: 0.014 amp
Identify the Manufacturer’s Name, Model
designation for appliances to be used on the circuit
or reference the device compatibility
section/document.
Refer to the Compatibility Addendum to Gamewell-
FCI Manuals, P/N: 9000-0427-L8.
Max. Line Impedance: 40 Ohms and .5 µF line capacitance
Ground Fault Test Impedance: Zero Ohms
Impedance values and ground faults are
annunciated.
GND FAULT LED or LCD-SLP
Identified by class or by class/style: One Class A, Style 6, Style 7 or Class B, Style 4
signaling line circuit.
Table 2.6.4.1 SLC-PM Signaling Line Circuit Specifications

Table of Contents

Related product manuals