EasyManuals Logo

Honeywell Gamewell FCI S3 Series User Manual

Honeywell Gamewell FCI S3 Series
60 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #14 background imageLoading...
Page #14 background image
14 S3 Series UL Listing Document — P/N LS10005-051GF-E:D3 3/09/2016
Installation Wiring SLP-E3 Main Circuit Installation Wiring Diagram
2.2.5 SLP-E3 Standby Battery Calculation Chart
Table 2.2.5.1 lists the SLP-E3 Standby Battery Calculations.
NOTES
NOTE 1: Four hour standby permitted for installations with automatic backup generators. 24, 60
hours as required by code. Use Table 2.2.5.1 to obtain the correct sized battery capacity
required.
NOTE 2: 5, 15, 30 or 60 minute Alarm duration as required by code. Use Table 2.2.5.1 to obtain
the correct sized battery capacity required.
Table 2.2.4.1 SLP-E3 Main Circuit Specifications
Qty Module Description
Supv.
Current
Alarm
Current
Total
Supv.
Current
Total
Alarm
Current
SLP-E3 Smart Loop Panel-Main Board 0.100 A 0.180 A
Resettable Auxiliary Power, max. 1.75 A
Non-Resettable Auxiliary Power, max. 1.75 A
Municipal, max. 0.75 A
Notification Appliances (See Note 6)
SLC-PM Signaling Line Circuit - Personality Board 0.014 A 0.014 A
Addressable Sensors & Modules (See Note 6)
Signaling Line Circuits (SLCs) (See Note 6)
SLC95-PM Signaling Line Circuit 95 - Personality Board 0.016 A 0.016 A
Addressable Sensors & Modules (See Note 6)
Signaling Line Circuits (SLCs) (See Note 6)
LCD-SLP LCD Display/Switch Control (See Note 3) 0.030 A 0.065 A
LCD-E3 LCD Display/Switch Control 0.024 A 0.028 A
ASM-16 Annunciator Switch Module 0.011 amp (with
no LEDs lit)
0.011 amp
(See Note 4)
ANU-48 Remote LED Driver Assembly 0.011 amp 0.011 amp
(See Note 5)
LCD-7100/
RAN-7100
Remote Display Module 0.12 A 0.23 A
DACT-E3 Digital Dialer Communication Transmitter 0.018 A 0.018 A
RPT-E3-UTP ARCNet Repeater 0.016 A 0.017 A
FML-E3 Fiber-Optic Multi-Mode Board 0.053 A 0.053 A
FSL-E3 Fiber-Optic Single Mode Board 0.079 A 0.079 A
User Calculation Totals
A Total Supervisory Current (See Note 6)
B Enter number of standby hours required (See Note 1)
C Multiply Line A times hours in Line B—enter
D Total alarm current from above
E Enter alarm sounding period in hours.
F Multiply Line D times Line E –enter
G Total of Lines C & F—enter
H Multiply Line G by 1.2 --- enter (Total ampere/hours required) (See Note 2)
NOTES
NOTE 1: 24 hours for NFPA 72 protected premises or Central Station signaling, or Auxiliary, or Remote Supervising
Station Fire Alarm Systems.
NOTE 2: Use the next size battery with a capacity greater than required. (Use only Gamewell-FCI Models: B-17R,
B-55R, BAT-12120, BAT-12260, or BAT-12550 batteries). The maximum standby current is 0.560 A for 60 hours
when using 55 A/H batteries.
To comply with FM standards, use 0.247 A for 90 hours when using 55 A/H batteries.
The system batteries must be replaced as a set.
Table 2.2.5.1 SLP-E3 Standby Battery Calculation Chart

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Honeywell Gamewell FCI S3 Series and is the answer not in the manual?

Honeywell Gamewell FCI S3 Series Specifications

General IconGeneral
BrandHoneywell
ModelGamewell FCI S3 Series
CategoryFire Alarms
LanguageEnglish

Related product manuals