48 S3 Series UL Listing Document — P/N LS10005-051GF-E:D3  3/09/2016
Functionality SLP Main Board Features
4.1.1 Default Display Priority
Table 4.1.1.1 lists the Default Display Priority of Signals.
UL Standard Functions
S3 Functionality
DARC Check In: No
Primary Power Source Failure: Yes
The primary power source failure of constantly attended supervising 
station equipment, for methods to determine when the fault condition 
is obvious to the operator on duty is covered in the instructions.
S3 Functionality:
Yes, the Primary Power Source Failure for the SLC System signals  
with an AC (green) LED that is lit only when the system is running 
from primary power.
DAC Communication Format: Yes (Refer to the DACT-E3 Installation Instructions, P/N: 9000-0581).
SIA (Refer to the DACT-E3 Installation Instructions, P/N: 9000-0581).
Contact ID (Refer to the DACT-E3 Installation Instructions, P/N: 9000-0581).
SK 4/2 (Refer to the DACT-E3 Installation Instructions, P/N: 9000-0581).
3/1 (Refer to the DACT-E3 Installation Instructions, P/N: 9000-0581).
Other
Interconnected Control Panels: Yes, the S3 panel has interconnected control panels.
Unless interconnected control units located at a protected premises 
are intended to be installed such that the display annunciation at each 
unit can be simultaneously observed, alarm, supervisory, and trouble 
conditions, as well as reset, alarm silence, or trouble silence actuation 
originating at any unit shall be annunciated at each control unit and 
non-supplementary operator interface.
S3 Functionality:
Yes, on the interconnected control panels, the displayed events are 
prioritized, so that users can view only the events that correspond to 
the same priority level as that of the highest priority active event. 
Walk Test: Yes
Integrated/Network Local Functionality: Yes, on the S3 System, the Integrated/Network Local Functionality 
can be used with a Daughter-Card.
Circuit disables: Yes
Mapping: No
Detection/Alarm Algorithms: Yes, on the S3 System, the detection/alarm algorithms follow the 
device Manufacturer’s specifications per the device response curves.
Day/Night Sensitivity: Yes
Detection Sensitivity Adjustment: No
Extent/Limitations of Combination 
System:
On the S3 FACP System, the extent/limitations of a combination 
system can be used to initiate and report CO Alarm Events, in 
addition to Fire Events.
Table 4.1.1 SLP Main Board Functionality  (Continued)
Condition Unacknowledged Acknowledged
Fire Alarm ALARM_PLUS (14) LOW (3)
CO/Gas Alarm ALARM (13) LOW (3)
Action HIGH (9) LOW (3)
Supervisory HIGH (9) LOW (3)
Trouble  MEDIUM (6) LOW (3)
NOTE: Priorities can be programmed for Site-Specific requirements.
Table 4.1.1.1   Default Display Priority