50 S3 Series UL Listing Document — P/N LS10005-051GF-E:D3 3/09/2016
Programming Options uIP Code License
Section 5: Programming Options
THE FOLLOWING ARE GAMEWELL-FCI PROGRAMMING SETTINGS
THAT WILL BE MODIFIED FOR CAMWORKS PROGRAMMING.
Notice to Users, Installers, Authorities Having Jurisdiction and Other Involved Parties:
This product uses the CAMWorks™ Programming. You cannot program this product from the Display Panel. To program
this product, you must contact your Gamewell-FCI Customer Support Representative to schedule a Factory Certified
Training Class. Basic programming options are done using an AUTO CONFIG program and are described in the next
Section.
This product incorporates field-programmable software. In order for the product to comply with the requirements in the
Standard for Control Units and Accessories for Fire Alarm Systems, UL 864, certain programming features or options must
be limited to specific values or not used at all as indicated in the Table 5.1.
5.1 uIP Code License
From uIP
©
uIP
©
is an open source software, licensed under the following BSD-style license:
Copyright (c) 2001-2006, Adam Dunkels and the Swedish Institute of Computer Science All rights reserved.
NOTE: NOTICE to users, installers, Authorities Having Jurisdiction (AHJ), and other involved parties:
This product incorporates field programmable software. In order for the product to comply with the requirements
in the Standard for Control Units and Accessories for Fire Alarm Systems, UL Standard 864 9th Edition, certain
programming features or options must be limited to specific values or not used at all as indicated below.
Programmable Feature Permitted in UL 864 Possible Settings
UL Permitted
Settings
Trouble Reminder Yes Enabled/Disabled Enabled (Default)
Supervisory Sounder Cadence Yes Steady/Pulsed Steady/Pulsed
PAS Acknowledge Time Yes 1 to 3600 Seconds 15 Seconds (Default)
PAS Investigate Time Yes 1 to 3600 Seconds 180 Seconds (Default)
Standard NAC Codes:
Yes
Steady (Default)
Temporal 3 (ANSI S3.41)
Temporal 3 Temporal 3
March Time 60 BPM March Time 60 BPM
March Time 120 BPM March Time 120 BPM
Steady Steady
California Code California Code
Coded 4’S Coded 4’S
DACT:
- Daily Max # of ALARM Reports Yes Unlimited or 5 to 315
by increments of 5
Unlimited (Default)
- Daily Max # of Supervisory Reports Yes Unlimited or 5 to 155
by increments of 5
10 (Default)
- Daily Max # of Trouble Reports Yes Unlimited or 5 to 155
by increments of 5
10 (Default)
AC Fail Reporting Delay by DACT Yes 1 to 31 hours 1 to 3 hours
Alarm Event Display Priority No CO Highest/Fire
Highest (Default)
FIRE is Highest Priority
Releasing Delay Yes CAMWorks Timer User
Programmable 1 to
3600 Seconds
Up to 60 Seconds
Maximum
Table 5.1 Programming Options
NOTE: SOFTWARE WARRANTY DISCLAIMER:
THIS SOFTWARE IS PROVIDED BY THE AUTHOR ‘AS IS’ AND ANY EXPRESS OR IMPLIED
WARRANTIES, INCLUDING, BUT NOT LIMITED TO, THE IMPLIED WARRANTIES OF MERCHANTABILITY
AND FITNESS FOR A PARTICULAR PURPOSE ARE DISCLAIMED. IN NO EVENT SHALL THE AUTHOR
BE LIABLE FOR ANY DIRECT, INDIRECT, INCIDENTAL, SPECIAL, EXEMPLARY, OR CONSEQUENTIAL
DAMAGES (INCLUDING, BUT NOT LIMITED TO, PROCUREMENT OF SUBSTITUTE GOODS OR
SERVICES; LOSS OF USE, DATA, OR PROFITS; OR BUSINESS INTERRUPTION). HOWEVER, CAUSED
AND ON ANY THEORY OF LIABILITY, WHETHER IN CONTRACT, STRICT LIABILITY, OR TORT
(INCLUDING NEGLIGENCE OR OTHERWISE) ARISING IN ANY WAY OUT OF THE USE OF THIS
SOFTWARE, EVEN IF ADVISED OF THE POSSIBILITY OF SUCH DAMAGE.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Honeywell Gamewell FCI S3 Series and is the answer not in the manual?

Honeywell Gamewell FCI S3 Series Specifications

General IconGeneral
BrandHoneywell
ModelGamewell FCI S3 Series
CategoryFire Alarms
LanguageEnglish

Related product manuals