INNCOM e7w THERMOSTAT USER GUIDE
5
31-00302-01
Wireless Communication
Parameter
Description
RF Data Rate
250 kbps
Antenna Type
SMT
Range
70ft
Transmit Power
+5 dBm
Receive Sensitivity
-95 dBm
Frequency Band
2.4 Ghz
Encryption
AES - 128
Protocol
802.15.4
Frequency Channels
11-26
Note: Required Deep Mesh Network 2.4 GHz
Approvals
EN
Product
Standard
EN 60730-1:2011 and EN 60730-2-9:2010
EMC
Standard
ETSI 301489-1 V2.2.1, ETSI 301 489-17 V 3.2.0 and EN 55032
UL
UL 60730-1, 5th edition and UL 60730-2-9, 4th edition.
IEC and EN EMC standards:
EU RoHs: EN 50581:2012 per EU RoHS Directive 2011/65/EU,
EN 50581:2012 per EU RoHS Directive 2011/65/EU.
CSA
CSA (IEC Based), Note 1 on standards,
Note 2 on aspects impacted by transition
CAN/CSA E60730-1, 5
th
edition
CAN/CSA E60730-2-9, 4
th
edition

Table of Contents