The e7w will continuously send four read commands to read the below values from the tar-
get device until the FC button is pressed. A successful ping will show the following four
parameter values in sequence:
1. Device Type Code
2. Major SW Version
3. Minor SW Version
4. AGC Level of Pinged Device
6. Press the FC button to stop pinging.
7. Press FC button twice to exit SERVICE MODE.
Verifying Entry Door Reporting
1. Enter SERVICE MODE on the e7w.
2. Press UP/DOWN arrow buttons to select dor.
3. Press MODE button. This action displays dor value (O is the default dor value displayed)
Perform the below steps:
a) Open the entry door.
b) The device in the room that is monitoring and reporting entry door position sends a
0x000281 Door Open message to the e7w.
c) The device in the room that is the Door Server sends a 0x0002981 Door Server Reports
Door Open message to the e7w.
4. After receiving 0x0002981 Door Server Reports Door Open message, the e7w plays a
buzzer sound and increment the displayed door open count.
5. The e7w stops the buzzer sound when the opened door is close.
6. Press FC button twice to exit SERVICE MODE.
Verifying Guest Occupancy Reporting
1. Enter SERVICE MODE on the e7w.
2. Press UP/DOWN arrow buttons to select Plr.
3. Press MODE button. This action displays Plr value (O00 is the default Plr value displayed)
Walk sideways in the front of the thermostat, so that PIR motion sensor can detect the vari-
ation in movement.
4. PIR (Passive Infrared) Motion sensor detects guest movement in the room, and e7w plays
beep sound and increment the detected motion count displayed.
5. The PIr motion test remains active for one minute, then automatically times out.