3. Press MODE button. This action display Win value (000 value displayed).
4. Open the monitored window. The following sequence should happen:
a) The device used for monitoring and reporting window door position sends a 0x0002A1
Window Open message into the room.
b) The device in the room with its Window Server enabled sends a 0x0002B01 Window
Server Reports window is Open message into the room.
c) Upon seeing the 0x0002B01 Window Server Reports Window Open, the e7w will sound
its buzzer, display for 1 second, then increment and display the Window open
count.
5. The e7w buzzer stops, when the window is closed. The window test automatically timeout
after one minute.
6. Press the FC button to return SERVICE MODE or press UP arrow button to display next
mode.
Or
Press the FC button twice to exit SERVICE MODE
BND – Binding Auxiliary Devices (bnd)
Use the bnd parameter to open a two minute bind window in a remote device. The typical use of this
feature is to use the e7w to open the Bind Window in a PC502.4G or Evora RF Lock proxy, when bind-
ing the PC502/Evora and RF Lock. The PC502/Evora does not have a user interface to open its Bind
Window, to configure PC502/Evora use e7w.
NOTE: Before you start configuring bnd mode, you need configure Room ID, PAN ID and RF Channel
in the e7w.
1. Enter SERVICE MODE
2. Press UP/DOWN arrow buttons to select Adr.
3. Press MODE button. This action displays Adr value.
4. Use the UP/DOWN arrow buttons to change the Adr value to target address. Set Adr value
to desired address (65 (Timelox locks installed) or 69 (Salto locks installed).)