INNCOM e7w THERMOSTAT USER GUIDE
RST – Resetting e7w (rSt)
rSt parameter is used to reset the e7w, reboot the e7w back to Factory default settings or Reset a
remote device.
1. Enter SERVICE MODE
2. Press UP/DOWN arrow buttons to select rSt.
3. Press MODE button. This action displays default value 0.
4. Press UP/DOWN button to the select the reset value.
For reset value, refer below table:
Reboot the e7w back to factory default settings
Address of in-room device to Reset. The e7w will send a 420 reset command
to this P5 address
5. Press the FAN button to execute the Reset.
6. Press the FC button to return SERVICE MODE or press UP arrow button to display
next mode.
Or
Press the FC button twice to exit SERVICE MODE.
WAN – Verifying Wide Area Network (WAn)
WAn mode is used to verify, if the Room Gateway device in the room is connected to the INNCOM
Server via its associated B574/B578 Edge Router or B576 Floor Bridge.
NOTE: This test mode only applies to a network or online installation
1. Enter SERVICE MODE
2. Press UP/DOWN arrow buttons to select WAn.