3. From the OPC Test Client from menu bar, select Server > Connect…
4. In dialog window, select FactoryTalk Gateway and enter network name or IP address of the
Vertex M system in the Node Name field. A connection is established once the network
name or IP address of the Vertex server will appear in the application main window header.
5. Once connected, create a group. From OPC Test Client menu bar, select Group > Add
Group…
6. For the Group Name field, enter a desired name for the group to create, then OK. The newly
created group should appear with the name used in the OPC Test Client left panel.
Vertex M 247 User Manual