12.6 PWM Examples
All of the PWM examples use the following formula.
Frequency =
( )
tPe riodCounescale ď‚´+1Pr
000,000,32
Example 1
To get a 50% Duty Cycle @ 10 kHz waveform on PWM1:
Set %AQ1 = 50 (duty cycle count)
Set %AQ5 = 30 (prescale count)
Set %AQ7 = 100 (period count)
Example 2
To get a 50% Duty Cycle on PW1 and 90 % Duty Cycle on PWM2 @ 1 kHz waveform:
Set %AQ1 = 500 (duty cycle count)
Set %AQ3 = 900 (duty cycle count)
Set %AQ5-6 = 30 (prescale count)
Set %AQ7-8 = 1000 (period count)
Example 3
To turn PWM 1 output ON all the time
Set %AQ1-2 = Same value as AQ7-8 (duty cycle count)
Set %AQ5-6 = Any value (prescale count)
Set %AQ7-8 = Non-Zero value (period count)
Example 4
To turn PWM 1 output OFF all the time
Set %AQ1-2 = 0 (duty cycle count)
Set %AQ5-6 = Any value (prescale count)
Set %AQ7-8 = Any value <or> 0 (period count)