12 LFF / 24 SFF DAC All 30°C (86°F)
AOC All 25°C (77°F)
Drive configurationDrive configuration Cable typeCable type Processor TDPProcessor TDP Maximum inlet ambientMaximum inlet ambient
temperaturetemperature
Limited operating inlet ambient temperature requirements for Limited operating inlet ambient temperature requirements for HPEHPE NS204i Boot Device NS204i Boot Device
IMPORTANT:IMPORTANT:
When used in high performance compute workloads, the HPE NS204i Boot Device might cause the fans to operate at
high speeds to maintain optimum system cooling. This high-speed fan operation can generate excessive fan noise and
lead the system to be on standby mode.
Drive configurationDrive configuration Fan configurationFan configuration Maximum inlet ambient temperatureMaximum inlet ambient temperature
4 LFF / 8 SFF Four fans (Fans 1–4), nonredundant 30°C (86°F)
Eight fans (Fans 1–8), redundant 30°C (86°F)
8 LFF / 16 SFF Four fans (Fans 1–4), nonredundant 30°C (86°F)
Eight fans (Fans 1–8), redundant 30°C (86°F)
8 NVMe x4 Four fans (Fans 1–4), nonredundant 30°C (86°F)
Eight fans (Fans 1–8), redundant 30°C (86°F)
12 LFF / 24 SFF Four fans (Fans 1–4), nonredundant 25°C (77°F)
Eight fans (Fans 1–8), redundant 30°C (86°F)
Mechanical specificationsMechanical specifications
Tower orientationTower orientation
SpecificationSpecification ValueValue
DimensionsDimensions —
Height (with chassis feet) 46.2 cm (18.19 in)
Depth 71.26 cm (28.06 in)
Width 17.4 cm (6.85 in)
Weight, approximate valuesWeight, approximate values —
Minimum 23.48 kg (51.76 lb)
Maximum 36.61 kg (80.71 lb)
Rack orientationRack orientation
SpecificationSpecification ValueValue
DimensionsDimensions —
Height 17.4 cm (6.85 in)
Depth 71.26 cm (28.06 in)
Width 44.50 cm (17.52 in)
Weight, approximate valuesWeight, approximate values —