EasyManua.ls Logo

HT FULLTEST3 - Prospective Short Circuit Current Calculation

HT FULLTEST3
100 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
FULLTEST3
EN - 53
6.6.2. Prospective short circuit current calculation
LIMIT
mode
TT system
Evaluation condition
TN system
Evaluation condition
L/L
STD No evaluation No evaluation
kA ISC L/L MAX 3PH < BC ISC L/L MAX 3PH < BC
I
2
t
(ISC L/L MAX 3PH)
2
× t < (K × N
× S)
2
(ISC L/L MAX 3PH)
2
× t < (K × N
× S)
2
TRIP
CURR.
ISC L/L MIN 2PH o Tmax,
Tmax < Tlim
ISC MIN 2PH o Trip time T, T <
Tlim
Ut
L/N
STD No evaluation No evaluation
kA ISC L/L MAX 3PH < BC ISC L/L MAX 3PH < BC
I
2
t
(ISC L/N MAX)
2
× t < (K × N ×
S)
2
(ISC L/N MAX)
2
× t < (K × N × S)
2
TRIP
CURR.
ISC MIN 2PH o Trip time T, T <
Tlim
ISC MIN 2PH o Trip time T, T <
Tlim
Ut
L/N
STD No evaluation No evaluation
kA ISC MAX L/N < BC ISC MAX L/N < BC
I
2
t
(ISC MAX L/N)
2
× T < (K × N ×
S)
2
(ISC MAX L/N)
2
× T < (K × N ×
S)
2
TRIP
CURR.
ISC MIN L/N o Trip time T, T <
Tlim
ISC MIN L/N o Trip time T, T <
Tlim
L/PE
STD No evaluation No evaluation
kA ISC MAX L/PE < BC ISC MAX L/PE < BC
I
2
t
(ISC MAX L/PE)
2
× T < (K × N ×
S)
2
(ISC MAX L/PE)
2
× T < (K × N ×
S)
2
TRIP
CURR.
ISC MIN L/PEo Trip time T,T<T
lim
ISC MIN L/PEo Trip time T, T <
Tlim
Ut ISC MIN L/PE > N × In ISC MIN L/PE > N × In
where:
BC = breaking capacity of the protection
T = Trip out time according to the characteristic and nominal current of used
protection device
K = see the below table
Material/Coating
PVC Natural / Butyl rubber EPR/XLPE
Cu (Copper) K = 115 K = 135 K = 143
Al (Aluminum) K = 76 K = 87 K = 94
N = Number of conductors
S = Cross section of a conductor
For calculation of short-circuit current I
SC nominal voltage Un of mains installation is
needed, so it must be selected in prior to the measurements. How to select the
nominal voltage Un: Press the MENU o SETUP o NOMINAL VOL. touch-screen
keys and select the desired value (see § 5.5)
3. Check selected measurement mode (LOOP L/N, LOOP L/L, LOOP L/PE, IMP57
L/N, IMP57 L/L or IMP57 L/PE) and modify it if needed by pressing the MODE
touch-screen key first

Table of Contents

Related product manuals