5.5.1. Reset Menu
There are many adjustable parameters in the FULLTEST3 tester. If an operator due
to any reason wishes to reset all adjustable parameters to factory-set values, the
operation can be done by using the RESET menu. Confirm RESET operation by
pressing the YES touch-screen key or press the EXIT hard key to exit the menu. Turn
the tester off and on again by using the ON/OFF mains switch. The Reset operation
DOES NOT delete the data saved inside the memory
Function Parameter
GENERAL - OPERATOR = Default
- LANGUAGE = ITALIAN
- CONTACT VOLTAGE = 50 V
- NOMINAL VOLTAGE = 230 V
- SAFETY INPUT = ENABLED
- SOUND = ON
RPE-2WIRE - Im NOM = 200 mA
- LIMIT value (200 mA) = 0.30 :
- MODE = MANUAL
- CAL (200 mA) = 0.00 :
- LIMIT value 1 (200 mA) = 0.30 :
- LIMIT value 2 (200 mA) = 1.00 :
- LIMIT value 3 (200 mA) = 5.00 :
- LIMIT value 4 (200 mA) = 50.0 :
- LMIT mode (25 A) = STANDARD
- LIMIT value (25 A, STANDARD limit mode) = 0.30 :
- LIMIT value 1 (25 A, STANDARD limit mode) = 0.30 :
- LIMIT value 2 (25 A, STANDARD limit mode) = 1.00 :
- LIMIT value 3 (25 A, STANDARD limit mode) = 5.00 :
- LIMIT value 4 (25 A, STANDARD limit mode) = 10.0 :
- LENGTH = 2 m
- LENGTH 1 = 2 m
- LENGTH 2 = 3 m
- LENGTH 3 = 10 m
- LENGTH 4 = 100 m
- SECTION = 1 mm
2
- SECTION 1 = 1 mm
2
- SECTION 2 = 2.5 mm
2
- SECTION 3 = 10 mm
2
- SECTION 4 = 35 mm
2
- MAT. = Cu
- Z
LINE = 0.100 :
- Z
LINE 1 = 0.100 :
- Z
LINE 2 = 0.300 :
- Z
LINE 3 = 0.500 :
- Z
LINE 4 = 1.000 :
- PROTECTION = MCB B
- I
N (any protection) = 6 A
- I
N (any protection) 1 = 6 A
- I
N (any protection) 2 = 16 A
- I
N (any protection) 3 = 25 A
- I
N (any protection) 4 = 32 A
- TIMER = 3 s
- TIMER 1 = 3 s
- TIMER 2 = 10 s
- TIMER 3 = 30 min
- TIMER 4 = 60 min
- CAL (25 A) = 0.000 :