Step 1 Connect teamwork and monitoring communications cables.
Networking CAN Teamwork RS485 Monitoring
Protocol CAN Modbus-RTU
Description One teamwork network
supports a maximum of 32
units. On the Teamwork
Settings screen of the display
modules of the rst and last
units, set Enable teamwork
CAN resistor to Yes.
It takes 3 x
n
seconds to
collect data from
n
units. If
the time required for the host
to collect data from all units
does not meet the
performance requirements,
group the units.
If units are not grouped (
n
= 1), set RS485 monitoring
grouping to Enable on the
Modbus Settings screen
for each unit.
If units are grouped (
n
> 1;
recommended:
n
≤ 4), set
RS485 monitoring
grouping to Enable on the
Modbus Settings screen
for the unit with the
COM/FE port connected.
Retain the default setting
(Disable) for other units.
NO TE
Connect the COM/FE port on the main control module of the last unit in each group to
the RS485 port on the host.
Customers can purchase an ECC and NetEco as the monitoring system.
NetCol5000-A050 In-row Air Cooled Smart Cooling
Product
User Manual 4 Installation
Issue 08 (2021-09-17) Copyright © Huawei Technologies Co., Ltd. 113

Table of Contents

Other manuals for Huawei NetCol5000-A050

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Huawei NetCol5000-A050 and is the answer not in the manual?

Huawei NetCol5000-A050 Specifications

General IconGeneral
BrandHuawei
ModelNetCol5000-A050
CategoryComputer Hardware
LanguageEnglish

Related product manuals