Figure 12-18 Delete historical alarms screen
Step 2 Tap Conrm to delete all historical alarms.
NO TE
After alarms are deleted, the operation is recorded in logs.
----End
12.13 How Do I Clear Component Runtime?
Context
NO TICE
Performance value clearance can be performed only after component
maintenance. Otherwise the component may run overtime and degrade
performance.
Procedure
Step 1 On the home screen, choose Maint > Performance Maint.
Step 2 Tap Clear of a specic performance parameter to clear its runtime.
----End
12.14 How to Calibrate a Sensor
Context
Calibrate a sensor if the displayed temperature or humidity on the sensor deviates
from the actual value. For example, if the return air temperature measured by
other temperature detection devices at the return air detection point is 20°C while
NetCol5000-A050 In-row Air Cooled Smart Cooling
Product
User Manual 12 FAQ
Issue 08 (2021-09-17) Copyright © Huawei Technologies Co., Ltd. 304