EasyManua.ls Logo

Huawei NetCol5000-A050 - Page 220

Huawei NetCol5000-A050
360 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Alarm
ID
Alarm Name Alar
m
Seve
rity
Possible Cause Solution
A179-0
1
Humidier
function
abnormal
alarm
MAJ
OR
1. The humidier
pump inlet is
blocked.
2. The oat does
not drop because
the
humidier
oat is faulty.
3. The cable to the
humidier pump is
not connected
properly.
4. The
humidier
pump is faulty.
5. The water pump
is blocked.
1. Clear the blockage
from the humidier
pump inlet.
2. Maintain the
humidier oat.
3. Check the cable
connection to the
humidier pump.
4. Replace the
humidier pump.
5. Replace the water
pump.
A180-0
1
Humidier
exceed
runtime alarm
WAR
NIN
G
The accumulated
runtime of the wet
lm of the
humidier exceeds
the alarm
threshold.
1. Maintain or replace
the wet lm of the
humidier and clear the
accumulated runtime.
A182-0
1
Humidier
water supply
abnormal
alarm
MAJ
OR
1. The humidier
water supply is
insucient.
2. The oat does
not oat because
the
humidier
oat is faulty.
3. The cable to the
humidier oat is
not connected
properly.
4. The cable to the
humidier water
inlet solenoid
valve is not
connected
properly.
5. The
humidier
water inlet
solenoid valve is
faulty.
1. Check the
humidier
water supply.
2. Maintain the
humidier oat.
3. Check the cable
connection to the
humidier oat.
4. Check the cable
connection to the
humidier water inlet
solenoid valve.
5. Replace the
humidier water inlet
solenoid valve.
NetCol5000-A050 In-row Air Cooled Smart Cooling
Product
User Manual 9 Alarm Reference
Issue 08 (2021-09-17) Copyright © Huawei Technologies Co., Ltd. 210

Table of Contents

Other manuals for Huawei NetCol5000-A050