Figure 2-4 Holes in the smart cooling product
(1) Power cable hole (Φ28 mm) on the top (2) Humidier water inlet pipe hole (Φ43 mm)
on the top
(3) Signal cable hole (Φ28 mm) on the
skylight
(4) Refrigerant gas pipe hole (Φ43 mm) on the
top
(5) Refrigerant liquid pipe hole (Φ43 mm) on
the top
(6) Drainpipe hole (Φ43 mm) on the top
(7) Signal cable holes (Φ28 mm) on the top (8) Power cable hole (Φ28 mm) at the bottom
(9) Humidier water inlet pipe hole (Φ43 mm)
at the bottom
(10) Refrigerant gas pipe hole (Φ60 mm) at
the bottom
(11) Drainpipe hole (Φ60 mm) at the bottom (12) Refrigerant liquid pipe hole (Φ60 mm) at
the bottom
(13) Signal cable hole (Φ28 mm) at the
bottom
Interior Components
The NetCol5000-A mainly consists of a DC variable-frequency compressor, EC fan,
evaporator, electronic expansion valve (EEV), oil separator, sight glass,
lter dryer,
air lter, electric heater (optional), wet lm humidier (optional), condensate
pump (optional),
dierential pressure switch, and temperature and humidity
sensor (T/H sensor).
NetCol5000-A050 In-row Air Cooled Smart Cooling
Product
User Manual 2 Product Description
Issue 08 (2021-09-17) Copyright © Huawei Technologies Co., Ltd. 16