Item Technical Specications
Humidity range 5%–90% RH
Storage
temperature
–40°C to +70°C
Storage humidity 5%–95% RH (non-condensing)
Inlet water
temperature range
of chilled water
10°C to 37°C
Highest operating
temperature of the
refrigerant side
125°C
Highest operating
temperature of the
cooling water
60°C
Water ow rate
9.5 m
3
/h
Water-side pressure
bearing
1.2 MPa
Refrigerant-side
pressure bearing
4.35 MPa
IP rating IP21
Altitude 0–4000 m (derated when the altitude is greater than 1000
m)
Environment Enclosed indoor environment in which the temperature
and humidity can be controlled within the ranges of 4°C
to 45°C and 5% RH to 90% RH respectively. If the indoor
installation position is ventilated, it should be more than
3.7 km away from the sea or pollution sources (such as
salt lakes, chemical plants, mineral plants, thermal power
plants, and coal mines).
Dimensions (H x W
x D) (mm)
530 x 1510 x 262
Net weight 63 kg
NetCol5000-A050 In-row Air Cooled Smart Cooling
Product
User Manual 3 Technical Specications
Issue 08 (2021-09-17) Copyright © Huawei Technologies Co., Ltd. 32

Table of Contents

Other manuals for Huawei NetCol5000-A050

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Huawei NetCol5000-A050 and is the answer not in the manual?

Huawei NetCol5000-A050 Specifications

General IconGeneral
BrandHuawei
ModelNetCol5000-A050
CategoryComputer Hardware
LanguageEnglish

Related product manuals