Table 6-1 Quick Settings
Item Description Setting Value Range
Voltage
level(V)
Species the system output
voltage level. This
parameter is congurable
only after the inverter is
shut down.
Set as
required.
-
Frequency
level(Hz)
Species the system output
frequency level. This
parameter is congurable
only after the inverter is
shut down.
Set as
required.
50, 60, and
automatic.
The default
value is 50.
System time Synchronizes the system
time to the UPS.
- -
Battery type Species the type of
batteries connected to the
UPS.
VRLA batt. VRLA batt.,
Lithium batt.
The default
value is VRLA
batt.
Single
battery
voltage (V)
Species the voltage of
each battery in a battery
string connected in series.
Set this parameter based
on the actual conguration.
This parameter is
congurable in non-
battery mode.
Set as
required.
2, 6, and 12.
The default
value is 0.
Batteries in a
battery
string
Species the number of
batteries in a battery string.
Set this parameter based
on the actual conguration.
This parameter is
congurable in non-
battery mode.
Set as
required.
The value
range
depends on
the voltage of
a single
battery. The
default value
is 0.
Single
battery
capacity
(Ah)
Species the capacity of
each battery in a battery
string connected in series.
This parameter is
congurable in non-
battery mode.
Set as
required.
7–1000. The
default value
is 0.
Number of
battery
strings
Species the number of
battery strings connected in
parallel. This parameter is
congurable in non-
battery mode.
Set as
required.
1–4. The
default value
is 0.
UPS2000-H-(6 kVA-10 kVA)
User Manual 6 Power-On Commissioning