Icon Name Color Status Description
50% ≤ Load rate < 75%
25% indicator: steady on
50% indicator: steady on
75% indicator: When the load
rate is 50%, the indicator is
o. When the load rate is
greater than 50%, the
indicator blinks.
Other indicators: o
75% ≤ Load rate < 100%
25% indicator: steady on
50% indicator: steady on
75% indicator: steady on
100% indicator: When the
load rate is 75%, the
indicator is o. When the
load rate is greater than 75%,
the indicator blinks.
Load rate ≥ 100%
The four indicators are steady
on.
2.4.4 UPS Button Functions
Table 2-2 UPS button functions
Button
Function Description
Starting the
inverter
When the UPS works in bypass mode (the bypass indicator is
on), hold down the button on the UPS for more than 5s.
Release the button when the inverter indicator blinks and you
hear a beep sound. Do not press any button during inverter
startup. When the startup command is successfully delivered,
and the inverter indicator is steady on, the UPS enters normal
mode.
Shutting down the
inverter
When the UPS works in inverter mode, hold down the button
on the UPS for more than 5s. Release the button when the
inverter indicator blinks and you hear a beep sound. Do not
press any button during inverter shutdown. When the
shutdown command is successfully delivered, and the inverter
indicator is o, the UPS shuts down the inverter output and
enters bypass mode.
UPS2000-H-(6 kVA-10 kVA)
User Manual 2 Product Overview
Issue 03 (2023-08-20) Copyright © Huawei Digital Power Technologies Co., Ltd. 27