2.5 Product Congurations
Table 2-6 Typical UPS congurations
Conguratio
n
Application Scenario Description
Single UPS Supplies power to common loads. 6 kVA/10 kVA UPS: A maximum of four
lead-acid battery packs can be connected
in parallel.
Parallel
system
Supplies power to large-sized data
centers or important loads. It
features high reliability and strong
transient overload resistance
capability.
A maximum of four UPSs can be
connected in parallel.
6 kVA/10 kVA UPS: A maximum of four
lead-acid battery packs can be
connected in parallel.
NOTE
Only single-phase and three-phase inputs
support parallel connection.
Table 2-7 Conguration relationship between UPSs and battery packs
UPS Model
Number of Parallel UPSs
(n1)
Number of Battery Packs
(n2)
6 kVA 1 (single) 1–4
2 1–4
3 1–4
4 1–4
10 kVA 1 (single) 1–4
2 1–4
3 1–4
4 1–4
UPS2000-H-(6 kVA-10 kVA)
User Manual 2 Product Overview
Issue 03 (2023-08-20) Copyright © Huawei Digital Power Technologies Co., Ltd. 32