Model Wiring Terminal Numb
er of
Phase
s
Rated
Voltage
External
Circuit
Breaker
Cable
Cross-
Sectional
Area
Terminal
Type
AC
OUTPUT/AC
output PE
16 mm
2
OT-16 mm
2
-
M6-90°
bending
Battery
(lead-
acid
battery)
BATTERY/
Battery +
- 144 V DC
to 240 V
DC (12–20
PCS of 12
V
batteries)
100 A/2 P
(characteri
stic D)
2 x 6
mm
2
OT-16 mm
2
-
M6-90°
bending
BATTERY/
Battery –
2 x 6
mm
2
OT-16 mm
2
-
M6-90°
bending
BATTERY/
Battery PE
2 x 6
mm
2
OT-16 mm
2
-
M6-90°
bending
● a: In bypass mode, the UPS obtains power from phase A, and the input current is the total
three-phase current.
● Torque for tightening M6 screws: 4.8 N·m
 
● Purchase input and output power cables based on site requirements. You are advised to
use cables that comply with standards such as UL 758 or IEC 60228.
● Use power cables made of soft conductors that work at 90°C or even softer conductors.
If you use power cables made of solid conductors or twisted conductors, the cables may
fail to be connected.
5.1.5 Unpacking and Checking
Context
Figure 5-3 Transportation rules
UPS2000-H-(6 kVA-10 kVA)
User Manual 5 Installation and Cable Connection
Issue 03 (2023-08-20) Copyright © Huawei Digital Power Technologies Co., Ltd. 59