7.1.1 Monthly Maintenance
Table 7-1 Monthly maintenance checklist
Item Expected Result Troubleshooting Maintenance
Interval
Operating
environment
Ambient
temperature: –
5°C to +50°C;
temperature
derating
coecient: not
derated from –
5°C to +40°C;
0.9 from 41°C
to 45°C; 0.8
from 46°C to
50°C
Humidity: 0–
95% RH (non-
condensing)
If the
temperature or
humidity is
abnormal,
check the air
conditioner
status.
If the input
voltage is
abnormal,
check the
power grid and
input cable
connection.
Monthly
Power grid
environment
220 V AC/230 V
AC/240 V AC
(phase voltage)
If the input
voltage is
abnormal,
check the
power grid and
input cable
connection.
If the output
voltage is
abnormal,
check the UPS
running status
and check
whether an
alarm is
generated.
Monthly
UPS2000-H-(6 kVA-10 kVA)
User Manual 7 Maintenance
Issue 03 (2023-08-20) Copyright © Huawei Digital Power Technologies Co., Ltd. 119