Figure 5-64 About
(1) ESN
----End
5.7 Installing an rPDU and rPDU Cables
Step 1 Install the rPDU in an appropriate position based on site requirements.
Step 2 Install rPDU cables.
1. Connect the rPDU ground cable to the nearest ground point on the rack.
2. Connect one end of the power cable to the rPDU wiring port.
– If rPDU cables have been connected onsite, skip this step.
– Connect cables to the rPDU based on the type of the rPDU and the silk
screen on the wiring port. The following cable connection is for reference
only.
Figure 5-65 Connection position in horizontal PDU2000-16-1PH-8/0-B1
Figure 5-66 Connection position in vertical PDU2000-63-1PH-16/8-B1
UPS2000-H-(6 kVA-10 kVA)
User Manual 5 Installation and Cable Connection
Issue 03 (2023-08-20) Copyright © Huawei Digital Power Technologies Co., Ltd. 93