7.2.1 Monthly Maintenance
Table 7-4 Monthly maintenance checklist
Item Expected Result Troubleshooting Maintenance
Interval
Battery
managem
ent alarm
No battery
management alarm
is generated.
Identify the alarm cause
based on the alarm
information.
Monthly
Battery
appearanc
e
1. The surface is
clean and free of
stains.
2. The battery
terminals are
intact.
3. Batteries are free
from damage
and cracks.
4. Batteries are free
from acid
leakage.
5. Batteries are not
deformed or
bulged.
If an exception occurs,
contact technical support.
Monthly
Battery
operating
temperatu
re
1. The standard
battery operating
temperature is
25°C.
2. Battery charge
and discharge
conditions meet
the requirements
specied in the
battery
specications.
1. Identify the cause of
the abnormal battery
operating temperature.
2. If the fault persists,
contact technical
support.
Monthly
UPS2000-H-(6 kVA-10 kVA)
User Manual 7 Maintenance
Issue 03 (2023-08-20) Copyright © Huawei Digital Power Technologies Co., Ltd. 122