7.3.2 Capacity Test
Context
Before performing a capacity test, ensure that:
● The UPS works in normal mode, and the battery SOC has reached 100% for
two hours.
● No high temperature, charger fault, or discharger fault has occurred.
● The load rate ranges from 5% to 100%, and the load uctuation is less than
10%.
Procedure
Step 1 On the app, choose Cong > Control.
Step 2 Set the Capacity test after all conditions are met. Tap Capacity test and the test
starts after about 5s.
Step 3 Tap Stop test to forcibly stop the capacity test.
----End
7.3.3 Test Data Download
Procedure
Step 1 On the WebUI, choose Query > Battery Test Records, choose logs that need to be
queried from the Log drop-down list, and click Query.
Figure 7-2 Battery Test Records
Step 2 Choose logs that have been queried from the Log drop-down list, and click
Export.
----End