B Lead-Acid Battery Backup Time
NO TE
The following table lists the backup time upon factory delivery, which decreases with the battery
capacity. The table is for reference only.
Table B-1 Backup time parameters for the battery pack ESS-240V12-7AhBPVA04
(6 kVA UPS; calculated based on 90% battery eciency)
Load (%)
Load (W) One
Battery
Pack
(min)
Two
Battery
Packs
(min)
Three
Battery
Packs
(min)
Four
Battery
Packs
(min)
100 6000 5 15 27 35
80 4800 8 20 36 49
50 3000 15 35 59 83
30 1800 30 65 110 164
Table B-2 Backup time parameters for the battery pack ESS-240V12-9AhBPVBA04
(6 kVA UPS; calculated based on 90% battery eciency)
Load (%)
Load (W) One
Battery
Pack
(min)
Two
Battery
Packs
(min)
Three
Battery
Packs
(min)
Four
Battery
Packs
(min)
100 6000 8 19 33 42
80 4800 9 29 44 58
50 3000 19 44 78 110
30 1800 36 87 147 206
UPS2000-H-(6 kVA-10 kVA)
User Manual B Lead-Acid Battery Backup Time
Issue 03 (2023-08-20) Copyright © Huawei Digital Power Technologies Co., Ltd. 136