Button Function Description
Enabling WiFi When the WiFi is disabled, hold down the button for less than
0.5s to enable the WiFi (the WiFi indicator turns on).
Disabling WiFi When the WiFi is enabled, hold down the button for less than
0.5s to disable the WiFi (the WiFi indicator turns o).
Cold-starting the
UPS using
batteries
1. Hold down the UPS button for 3s. The UPS starts in battery
mode and enters the standby state. The bypass indicator,
battery indicator, and inverter indicator turn on at the same
time. The UPS starts and enters the initialization state
(about 10s). The indicator status changes. The WiFi
indicator turns on, the fault indicator blinks, and the UPS
enters the standby state.
2. Hold down UPS button for more than 5s to start the UPS
inverter. The UPS enters battery mode.
NOTE
When the mains is abnormal or disconnected, start the UPS using
batteries.
Resetting the UPS Hold down the RESET button on the UPS rear panel for about
10s (all indicators turn o and then work properly) to restore
the preset WiFi password, preset user password, and SNMP
card (if any) IP address. Other parameters will not be restored.
2.4.5 Port Functions
Table 2-3 Functions of ports on the 6 kVA UPS
Port
Silk Screen Function
PE Connect battery cables.
BAT+/Battery +
BAT-/Battery –
IN_N/Input N Connect input cables.
IN_L/Input L
OUT_N/Output N Connect output cables. The output (OUT)
SL port connects to primary loads, and the
output (OUT) PL port connects to secondary
loads.
OUT_SL/Output SL
OUT_PL/Output PL
EPO Emergency power-o
UPS2000-H-(6 kVA-10 kVA)
User Manual 2 Product Overview
Issue 03 (2023-08-20) Copyright © Huawei Digital Power Technologies Co., Ltd. 28