EasyManua.ls Logo

Huawei UPS2000-H - Page 66

Huawei UPS2000-H
152 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Model Wiring Terminal Numb
er of
Phase
s
Rated
Voltage
External
Circuit
Breaker
Cable
Cross-
Sectiona
l Area
Terminal
Type
BATTERY/
Battery PE
2 x 6
mm
2
OT-16 mm
2
-
M6-90°
bending
Torque for tightening M6 screws: 4.8 N·m
Table 5-3 Recommended power cable specications (10 kVA UPS, three-phase input single-phase
output)
Model Wiring Terminal Numb
er of
Phase
s
Rated
Voltage
External
Circuit
Breaker
Cable
Cross-
Sectional
Area
Terminal
Type
10 kVA
(three-
phase
input
single-
phase
output)
Input AC
INPUT/AC
input L1
3 380 V
AC/400 V
AC/415 V
AC
80 A
a
/4 P
(characteri
stic D)
16 mm
2
OT-16 mm
2
-
M6-90°
bending
AC
INPUT/AC
input L2
16 mm
2
OT-16 mm
2
-
M6-90°
bending
AC
INPUT/AC
input L3
16 mm
2
OT-16 mm
2
-
M6-90°
bending
AC
INPUT/AC
input N
16 mm
2
OT-16 mm
2
-
M6-90°
bending
AC
INPUT/AC
input PE
16 mm
2
OT-16 mm
2
-
M6-90°
bending
Output AC
OUTPUT/AC
output SL
1 220 V
AC/230 V
AC/240 V
AC
63 A/2 P
(characteri
stic C)
16 mm
2
OT-16 mm
2
-
M6-90°
bending
AC
OUTPUT/AC
output PL
16 mm
2
OT-16 mm
2
-
M6-90°
bending
AC
OUTPUT/AC
output N
16 mm
2
OT-16 mm
2
-
M6-90°
bending
UPS2000-H-(6 kVA-10 kVA)
User Manual 5 Installation and Cable Connection
Issue 03 (2023-08-20) Copyright © Huawei Digital Power Technologies Co., Ltd. 58

Table of Contents

Related product manuals