Model Wiring Terminal Numb
er of
Phase
s
Rated
Voltage
External
Circuit
Breaker
Cable
Cross-
Sectiona
l Area
Terminal
Type
BATTERY/
Battery PE
2 x 6
mm
2
OT-16 mm
2
-
M6-90°
bending
Torque for tightening M6 screws: 4.8 N·m
 
Table 5-3 Recommended power cable specications (10 kVA UPS, three-phase input single-phase
output)
Model Wiring Terminal Numb
er of
Phase
s
Rated
Voltage
External
Circuit
Breaker
Cable
Cross-
Sectional
Area
Terminal
Type
10 kVA
(three-
phase
input
single-
phase
output)
Input AC
INPUT/AC
input L1
3 380 V
AC/400 V
AC/415 V
AC
80 A
a
/4 P
(characteri
stic D)
16 mm
2
OT-16 mm
2
-
M6-90°
bending
AC
INPUT/AC
input L2
16 mm
2
OT-16 mm
2
-
M6-90°
bending
AC
INPUT/AC
input L3
16 mm
2
OT-16 mm
2
-
M6-90°
bending
AC
INPUT/AC
input N
16 mm
2
OT-16 mm
2
-
M6-90°
bending
AC
INPUT/AC
input PE
16 mm
2
OT-16 mm
2
-
M6-90°
bending
Output AC
OUTPUT/AC
output SL
1 220 V
AC/230 V
AC/240 V
AC
63 A/2 P
(characteri
stic C)
16 mm
2
OT-16 mm
2
-
M6-90°
bending
AC
OUTPUT/AC
output PL
16 mm
2
OT-16 mm
2
-
M6-90°
bending
AC
OUTPUT/AC
output N
16 mm
2
OT-16 mm
2
-
M6-90°
bending
UPS2000-H-(6 kVA-10 kVA)
User Manual 5 Installation and Cable Connection