Model Wiring Terminal Numb
er of
Phase
s
Rated
Voltage
External
Circuit
Breaker
Cable
Cross-
Sectional
Area
Terminal
Type
Torque for tightening M4 screws: 1.2 N·m
Table 5-2 Recommended power cable specications (10 kVA UPS, single-phase input single-phase
output)
Model Wiring Terminal Numb
er of
Phase
s
Rated
Voltage
External
Circuit
Breaker
Cable
Cross-
Sectiona
l Area
Terminal
Type
10 kVA
(single-
phase
input
single-
phase
output)
Input AC
INPUT/AC
input L2
1 220 V
AC/230 V
AC/240 V
AC
80 A/2 P
(characteri
stic D)
16 mm
2
OT-16 mm
2
-
M6-90°
bending
AC
INPUT/AC
input N
16 mm
2
OT-16 mm
2
-
M6-90°
bending
AC
INPUT/AC
input PE
16 mm
2
OT-16 mm
2
-
M6-90°
bending
Output AC
OUTPUT/AC
output SL
1 220 V
AC/230 V
AC/240 V
AC
63 A/2 P
(characteri
stic C)
16 mm
2
OT-16 mm
2
-
M6-90°
bending
AC
OUTPUT/AC
output PL
16 mm
2
OT-16 mm
2
-
M6-90°
bending
AC
OUTPUT/AC
output N
16 mm
2
OT-16 mm
2
-
M6-90°
bending
AC
OUTPUT/AC
output PE
16 mm
2
OT-16 mm
2
-
M6-90°
bending
Battery
(lead-
acid
battery)
BATTERY/
Battery +
- 144 V DC
to 240 V
DC (12–20
PCS of 12
V
batteries)
100 A/2 P
(characteri
stic D)
2 x 6
mm
2
OT-16 mm
2
-
M6-90°
bending
BATTERY/
Battery –
2 x 6
mm
2
OT-16 mm
2
-
M6-90°
bending
UPS2000-H-(6 kVA-10 kVA)
User Manual 5 Installation and Cable Connection
Issue 03 (2023-08-20) Copyright © Huawei Digital Power Technologies Co., Ltd. 57