Table 3-3 Mains input electrical specications
Item 6 kVA 10 kVA
Single-Phase
Input
Single-Phase
Input
Three-Phase
Input
Power system 1Ph (L/N) + PE 1Ph (L/N) + PE 3Ph (L1/L2/L3/N)
+ PE
Rated input
voltage
220 V AC/230 V
AC/240 V AC
220 V AC/230 V
AC/240 V AC
380 V AC/400 V
AC/415 V AC
Input voltage
range
Phase voltage: 80
V AC to 280 V AC
(When the
ambient
temperature
ranges from –5°C
to +40°C, the load
is linearly derated
from 100% to
40% when the
voltage ranges
from 176 V AC to
80 V AC.)
Phase voltage: 80
V AC to 280 V AC
(When the
ambient
temperature
ranges from –5°C
to +40°C, the load
is linearly derated
from 100% to
40% when the
voltage ranges
from 176 V AC to
80 V AC.)
Line voltage: 138
V AC to 484 V AC
(When the
ambient
temperature
ranges from –5°C
to +40°C, the load
is linearly derated
from 100% to
40% when the
voltage ranges
from 176 V AC to
80 V AC.)
Rated frequency 50 Hz/60 Hz
Frequency range 40–70 Hz
Input power
factor
≥ 0.99 (100% resistive load)
Generator input
capacity
Minimum: 1.35 times of the UPS rated capacity
Overvoltage
category
OVC II
Table 3-4 Bypass input electrical specications
Item
Specications
Power system Single-phase, three-wire
Input voltage 220 V AC/230 V AC/240 V AC
UPS2000-H-(6 kVA-10 kVA)
User Manual 3 Technical Specications
Issue 03 (2023-08-20) Copyright © Huawei Digital Power Technologies Co., Ltd. 44