EasyManua.ls Logo

Husky Altanium Matrix5 - 7.6.3 Temperature Setpoints

Husky Altanium Matrix5
248 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Temperature Setpoints 69
User Guide v 1.0 — February 2020 Making Adjustments
To give numbers and names to two or more zones, do the steps that follow:
1. Select the zones to be renamed.
2. Touch the Zone Edit drop-down tab.
3. Touch the Zone Name field and type a new zone name for all the selected zones.
You can also select frequently used zone names with the use of the keys that follow:
Zone
Probe
Tip
Nozzle
Sprue
Manifold
Bridge
Valve Gate
Not Used
4. Touch the Auto+ button.
7.6.3 Temperature Setpoints
The Temperatures Setpoints for each of the heaters in the mold must be specified. The
default setting is 177 °C (350 °F).
To change a setpoint of a zone, do the steps that follow:
1. Touch the zone to be changed.
2. Touch the Frequently Used drop-down tab.
3. Touch the Temperature Setpoint field and type a new setpoint value.
4. Touch the Accept button.
7.6.4 Alarm Window
The Alarm Window lets you specify a range of how many degrees great than or less than the
Temperature Setpoint will cause an alarm. The default Alarm Window setpoint is 6 °C (10 °F).
Alarm Example: Temperature Setpoint = 300 °F, Alarm Window = 10 °F
Temperatures greater than 310 °F or less than 290 °F will cause an alarm. If the Temperature
Setpoint is changed to 350 °F, then temperatures greater than 360 °F or less than 340 °F will
cause an alarm. The Alarm Window setpoint is the same number of degrees greater than and
less than the Temperature Setpoint.
To change the Alarm Window for a zone, do the steps that follow:
1. Touch the zone to be changed.
2. Touch the Frequently Used drop-down tab.
3. Touch the Alarm Window field and enter a new value.
4. Touch the Accept button.

Table of Contents

Related product manuals