SD1 Series Inverters Function Parameters
-36-
Function
code
Name Description Default
Modify
corresponds to the maximum frequency in
forward direction (function code P00.03
) and
-100.0% corresponds to the maximum frequency
in reverse direction (function code P00.03).
Note:
The pulse setting can only be input by
multi-function terminals HDI. Set P05.00 (HDI
input selection) to high-speed pulse input.
5: Set via simple PLC program
The inverter
runs at simple PLC program mode
when P00.06=5 or P00.07=5. Set P10 (simple
PLC and Preset
speed control) to select the
running frequency running direction, ACC/DEC
time and the keeping time of corresponding
stage. See the function description of P10 for
detailed information.
6: Set via Preset speed running
The inverter runs at Preset
speed mode when
P00.06=6 or P00.07
=6. Set P05 to select the
current running step and set P10
to select the
current running frequency.
The Preset speed has the priority when P00.06
or P00.07
does not equal to 6, but the setting
stage can only be the 1~
15 stage. The setting
stage is 1~15 if P00.06 or P00.07 equals to 6.
7: Set via PID control
The running mode of the inverter
is process PID
control when P00.06=7 or P00.07
=7. It is
necessary to set P09
. The running frequency of
the inverter is the value after PID effect. See P09
for the detailed information of the preset source,
preset value, and feedback source of PID.
8: Set via Modbus communication
The frequency is set by Modbus communication.
See P14 for detailed information.
9~11: Reserved